Calculation of volumetric air flow Total outside air volumetric flow for fan-assisted ventilation Nominal ventilation qv,ges,NL = max {qv,ges,NE,NL ;min(∑R,abqv,ges,R,ab,NL;1.2 x qv,ges,NE,NL)} qv,ges,NE,NL =1.0 x (-0.002 x ANE² + 1.15 x ANE + 11) qv,ges,NE,NL =1.0 x (-0.002 x 50² + 1.15 x 50 + 11) qv,ges,NE,NL = 64m³/h ∑R,abqv, ges, R, ab, NL = bathroom, kitchen ∑R,abqv, ges, R, ab, NL = 40 m³/h + 40 m³/h ∑R,abqv, ges, R, ab, NL = 80 m³/h ∑R,abqv, ges, R, ab, NL > qv,ges,NE,NL qv,ges,NL = 1.2 x qv,ges,NE,NL = 1.2 x 64m³/h = 76 m³/h Ventilation for humidity protection qv,ges,FL = qv,ges,NL x qv,ges,NE,FL = 76m³/h x 19 m³/h = 23 m³/h qv,ges,NE,NL 64m³/h Reduced ventilation qv,ges,RL = qv,ges,NL x qv,ges,NE,RL = 76m³/h x 44 m³/h = 52 m³/h qv,ges,NE,NL 64m³/h Nominal ventilation qv,ges,NL = max {qv,ges,NE,NL ;min(∑R,abqv,ges,R,ab,NL;1.2 x qv,ges,NE,NL)} qv,ges,NL = 1.2 x 64m³/h = 76 m³/h Intensive ventilation qv,ges,IL = qv,ges,NL x qv,ges,NE,IL = 76 m³/h x 83 m³/h = 99 m³/h qv,ges,NE,NL 64 m³/h Distribution of supply air Supply air factors fZuluft in accordance with DIN 1946-6, type of use, supply air factor Living 3.0 (±0.5) Eating 1.5 (±0.5) Sleeping 2.0 (±1.0) Child 2.0 (±1.0) Working 1.5 (±0.5) Guests 1.5 (±0.5) Calculation with selected supply air factors: Living 3.0 Sleeping 2.0 Total: 5.0 (3 x 15.2 m³/h = 46 m³/h) (2 x 15.2 m³/h = 30 m³/h) Total: 76 m³/h Calculation: 76 m³/h : 5 = 15.2 m³/h y t i l a u q r i a m o o R i l g n n n a p r o f s s a B i i g n n n a p l l a c i t c a r P r o f y d s b u S i s m e t s y s n o i t a l i t n e v i l g n n n a p e p m a S l i w e v r e v o t c u d o r P 41