Installation instructions
- Make sure you use mounting material which is sized for the purpose.
- Do not tension or crush internal shutter when installing. Make sure that the surface is flat.
- For wall/duct installation, observe installation position "TOP".
- Thermally insulate ventilation ducts properly. Allow for a condensation drain or condensate collector in riser. Risk of short circuit if condensation forms in the housing.
- Make a wall breakthrough/core drill hole.
Minimum core hole Ø 105 mm or 155 mm.
Recommendation: Use WH 100 or WH 150 wall sleeve with minimum core hole Ø 115 mm or 170 mm.
For AE 10/1, use ZM 11 mounting plate for rectangular wall breakthroughs. - Lay the power cable to the installation location and lead it at least 110 mm out of the wall.
- ATTENTION: Ensure correct installation of the cable grommet. If the power cable is inserted incorrectly into the housing or if the cable grommet is not inserted correctly, water/moisture may penetrate the housing → risk of short circuit, damage to device. If necessary, seal the cable grommet on site.
Minimum distances to the wall and ceiling
| A | B | C |
AE 10/1 | 250 | 22 | 61 |
AE 15/1 | 400 | 22 | 86 |