Product information

AKE is a control unit for dehumidifying rooms, especially cellars and other adjoining rooms. The unit is equipped with two combination sensors connected by cable. A controlled dehumidification takes place based on the comparison between the indoor climate and the outdoor climate. The unit is operated with 230 VAC and offers 2 spring-loaded terminals for the direct connection of supply and exhaust air fans with a total output of up to 600 watts.

Function of the dehumidification control

The controlled ventilation dehumidifies the rooms (cellars) through targeted removal of humid room air and simultaneous supplying of dry outside air.

For this purpose, the absolute humidity (aH) is determined as a measure of the water vapour content in the air using both combination sensors (those for indoor and outdoor spaces).

This measurement takes place immediately after switching on the unit. As soon as the absolute outside humidity is lower than the absolute inside humidity (aHoutside < aHinside) the AKE/1 control unit automatically switches on the connected fans and a dehumidification period begins (active time).

Ventilation and air extraction take place for roughly 12 minutes. Then the fan is switched off for a further 12 minutes so that the moist room air can mix with the dry air brought in from outside (passive time). After the waiting period has lapsed, the comparison of the inside and outside humidity is repeated.

If the absolute humidity of the outside air is found to be greater than that of the air inside the room (aHouter > aHinner), air is not exchanged. This prevents moist air from flowing in. The fan is only switched on again once the climate conditions make dehumidification possible.

Button 1

Manual ventilation

LED 1 (mode)

Operating mode

LED 2 (status)

Dehumidification status

 

Display

Function

LED 1: On

Automatic operating mode

LED 1: Blinking*

Manual ventilation

LED 1: Blinks twice with long pause

Frost protection

LED 2: On (in automatic operation)

Active time during dehumidification (Fan on)

LED 2: Off

Passive time during dehumidification (Fan off)

* Simultaneous blinking:

Simultaneous blinking of LED 1 or LED 2 indicates an operating mode or function. If both LEDs blink simultaneously, there is a fault, see Fault rectification.

 

Manual ventilation – button:

The AKE/1 switches the fan on and off fully automatically and in a manner optimised to demand. When off, the fan can be switched on manually with button 1 and manual ventilation therefore takes place. Manual operation is ended by again pressing button or automatically after approximately 30 minutes.

The fan cannot be switched off manually using the button when in the automatic operating mode.

Manual ventilation – external button/switch:

Optionally to button 1, manual operation can take place with an external button or switch, see Wiring diagrams ("T").

For this purpose, automatic button/switch detection is carried out during the first actuation, after power is supplied. A switch is considered to be connected if the switching contact is active for more than 3 seconds. Automatic detection restarts each time the button is pressed.

Manual ventilation with an external button is equivalent to using button 1.

If an external switch is connected, manual ventilation is switched on or off in accordance with the switch setting. Manual ventilation ends automatically after about 30 minutes.

Manual ventilation is also possible during frost protection.

 

Frost protection:

To prevent the room from cooling down, the unit has a frost protection function. This means that the fan automatically switches off at inside room temperatures of less than 5°C.

 

DIP switch

Garage dehumidification/frost protection:

Button 2

Setting the 0-10 volt output

 

Switching off garage dehumidification/frost protection:

To dehumidify garages, the frost protection function can be switched off via the DIP switch. If the frost protection function is active, the DIP switch is set to ON.

 

Additional 0-10 volt output for controlling EC fans:

3 speed ranges: for example

Button 2 = press 2 s = level 1 = 3.3 V

Button 2 = press 4 s = level 2 = 6.6 V

Button 2 = press 6 s = level 3 = 10 V

Button 2 = press 8 s = Reset

Damage to the building fabric due to manual ventilation

Too frequent manual ventilation can lead to room humidification if the outdoor conditions are humid.

Limited use in case of structural defects.

In the case of structural defects, water often enters the cellar through floors and ceilings.

In such cases, the ventilation system consisting of AKE/1 and fans can also be used for cellar dehumidification. The unit helps to dry out walls via a controlled air exchange. It cannot be used independently to achieve complete dehumidification.