Installation instructions
Provide fastening and sealing material on site. Use fastening and sealing material suitable for the installation situation.
- Position the outside air opening according to the specifications of your planning office.
- Install outside air opening with a slope of approx. 1...2 % to the exterior wall.
- Recommendation: Install outside air opening in the upper window area (right or left of the window) with an installation height of 2 to 2.20 m.
- The design cover must be removable for filter change. The installation location must be selected accordingly.
- Sound insulation is reduced with thinner wall thicknesses.
- The three sound insulation elements together must correspond to the length of the wall sleeve; otherwise reduced sound insulation.
- Further information and planning instructions can be found in the Practical Guide to Comfort Ventilation → www.maico-ventilatoren.com.