Connecting the fan electrically
Note prescribed tightening torques.
Components | Tightening torque |
---|---|
Terminal box cover: M4 stainless steel cylinder head bolts | 1.0 Nm |
Sheath terminal M7 x 0.75 mm | 0.7 Nm |
Motor terminals TK | 0.7 Nm |
- De-energise the system.
- Remove the four lock nuts from the weather protection hood and take off the hood.
- Remove the terminal box cover.
- Guide the power cable into the terminal box.
- Attach the required cable screw connections and blind plugs (provided by the customer) to the terminal box, guide the power cable through the cable screw connection into the terminal box and secure it with the tension relief.
Figure: Standard: 3-phase with single polarity
- Wire the fan to the electrics according to the circuit diagram → sticker in terminal box or corresponding wiring diagram in the appendix. Tightening torque of terminals 1 Nm. Ensure PE conductor connection.
- Install appropriate overload protection (PTC thermistor triggering system) → Overload protection chapter and Maico’s range of accessories at www.maico-ventilatoren.com.
- Put the terminal box cover on and screw it into place. NOTICE: Risk of short circuits if terminal box not watertight. Ensure correct line feedthrough and cable screw connections/blind plugs.
- Place weather protection hood on fan housing and screw down with the four lock nuts (tightening torque 10 Nm). Ensure that the fan’s protective grille is correctly installed too.
- Switch the mains fuse on.
- Move inspection switch into position (1/On).