Roof mounting
- Fit suitable insulation and sealing material on the contact surface to the DRD fan.
- Use suitable transport equipment (crane) to carefully lower DRD fan at the installation site. Observe safety instructions for transport. NOTICE: Ensure seal integrity with the flat roof/roof socket. Remove the transport equipment.
- Firmly screw fan’s metal base down onto flat roof/roof socket at the 4 holes (positions [X]) (tightening torque 20 Nm). Suitable mounting material is to be provided by the customer.
When using a duct shutter, ensure that the shutters are free to move (VKRI HV accessories for H/V variants), VKRI for HT variants).
With a free inlet on the intake side, fit an SGRI Maico protective grille (accessory) suitable for the nominal size as protection against accidental contact and intake.