ECA 100 ipro RCH

Fully automatic humidity control function

Normally, the fan runs in standard operation at a power level that is manually set or predefined through an RLS RC.

When starting up the RCH fan, this fan is set in line with the current relative room humidity. This humidity is saved as the first reference value. No further manual setting of a reference value is necessary.

If the relative humidity drops directly following the installation, this is saved as the new reference value. The lowest possible reference value is 48 % relative humidity. If the room humidity increases by 7%, the fan switches on automatically at power level 1 (78 m³/h).

If humidity falls below the reference value, the power level is also switched back:

The currently prevailing room humidity is saved as the new reference value.

A new reference value is also saved if the radio switch is operated during humidity operating mode.