Fault rectification
Malfunction | Cause, measures |
---|---|
Fan does not switch on. | No mains voltage. Check whether the mains fuse has failed. Switch on if necessary. Check service switch. Impeller blocked. Check impeller and clean if necessary. |
Motor’s thermal overload protection switches the fan off. | Motor too hot. Wait until motor and temperature limiter have cooled. Cool-down time can be up to 30 minutes. Only then switch the fan on again. |
Deposits on the impeller and in the housing caused by dust in the air. | Install air filter in duct system. Never clean the interior with water or a high-pressure cleaner. |
Impeller does not turn. | Switch off the fan with the service switch. Make sure that the impeller is not blocked by foreign bodies. |