Installation instructions
ATTENTION: Damage to unit/functional problems in the event of rubbing impeller. Do not fit the flange sleeve either twisted or crushed. Make sure that the surface is level.
ATTENTION: Risk of short circuits/damage to unit if condensation builds up in the fan housing.
- Observe minimum wall thickness:
EN 20, ENR 20, EN 25, ENR 25: 105 mm
EN 31, ENR 31: 130 millimeters - Observe the permissible load-bearing capacity of the wall/ceiling.
- Allow sufficient space to the wall or ceiling.
- Any installation position can be selected.
- Lay the power cable to the installation site, either surface-mounted or flush-mounted.
- Use mounting material suitable for base and of sufficient dimensions.
- Push the cable grommets through correctly, i.e. circular and slightly smaller than the cable, to ensure the degree of protection.
- Select the installation site where foreign objects will not be accidentally drawn in.
- For installation of the external shutter/shutter, see the corresponding installation instructions. Never dismantle them and only install them on a flat surface to ensure proper shutter function.
- For electrical external shutters with plug connections, disconnect the plug and wire the individual cable cores according to the relevant circuit diagram .