Approval provisions

Approval provision

ER-APB

ER-AP

Number of units per floor, residential unit or fire zone

Max. 3 fans or 3 connections

Max. 2 fans or 2 connections

Shaft wall

min. 35 mm , board materials (F90)

min. 35 mm , board material, any

Connection ducts inside the shaft

AFR 80 flexible aluminium duct between the main duct in the shaft and unit, max. 2 m long (→ approval).

Connection ducts outside the shaft

Steel folded spiral-seams duct, between the main duct in the shaft and the unit, max. 2 m long (→ approval).

Steel folded spiral-seams duct or flexible aluminium duct, between the main duct in the shaft and the unit, max. 2 m long (→ approval).

Duct elbows in the unit connection duct

Max. 90° bend,
ascending

Number of duct elbows permitted for wall installation

Max. 1 x 90°

Max. 2 x 90°

Number of duct elbows permitted for ceiling installation

Max. 2 x 90°

Max. 3 x 90°

Regulating equipment in the exhaust air duct

Not permitted

Wall/ceiling opening for DN 80 unit connection duct

Brickwork or concrete: 130 mm.

Board materials (F90): Outer Ø of pipe