Preparations for wall, shaft or ceiling installation without fire protection
- Carry out installation preparations as described: Requirements in line with approval. However, comply with the specifications suitable for the exhaust air system in accordance with the applicable fire protection regulations.
- Permissible connection ducts for connection without fire protection requirements:
- Shaft/wall installation: Flexible aluminium duct with DN 80 connection diameter, max. 2 m long, two 90° elbows.
- Ceiling installation (connection outside of the shaft): Steel folded spiral-seams duct and/or flexible aluminium duct with DN 80 connection diameter, max. 2 m long, two 90° elbows.
- Use suitable mounting material for installation without fire protection.