Fault rectification
Danger to life from electric shock.
- Prior to accessing the connection terminals, switch off all supply circuits. Switch off mains fuse, secure against being accidentally switched back on and position a visible warning sign.
Fault | Cause → Measure |
---|---|
Fan performance inadequate. | Dirty filter. → Replace filter. Locking hook not engaged. → Engage fan insert correctly. Incorrect duct diameter. → Check diameter of the main duct. Supply air cross section is too small. → Increase the supply air cross section. |
VZ, F and H models: No fan overrun.
| The external conductor L connected to terminal 1 is interrupted when the unit is switched off. → Connect unit as per wiring diagram. |
VZ models: Unit starts up immediately and stops immediately if is switched off. | Terminals 1 and 3 are reversed. → Connect unit as per wiring diagram.
|
Fan is too loud. | Dirty filter. → Replace filter. Fan insert incorrectly installed. → Insert fan insert correctly in accordance with these instructions. The main duct is undersized. → Re-calculate pressure losses. |
H model does not switch from base load to full load operation despite there being humidity in the room. | No rapid increase in humidity (7 % in 2 minutes) took place. |
H model no longer switches back to base load operation or off even after a long period in full load operation. | The level has not yet fallen below reference value. After 1 h, the valve automatically switches from full load operation to base load operation after an overrun time of 15 minutes and resets the reference value. |
Additional consumers connected to terminal 4. | Damage to the unit if connected incorrectly. Do not connect additional consumers to terminal 4. The unit may only be connected according to the wiring diagrams (Wiring diagrams). |
: Disconnect the unit completely from the power supply. Let a qualified electrician determine the cause of the fault and eliminate it. If you have any question relating to troubleshooting: Service: +49 7720 6940.