Approval provisions

Approval provision

ER GH

Number of units per floor, residential unit or fire zone

Max. 3 fans or 3 connections

Connection diameter

DN 75 or DN 80

Shaft wall

Any board material

Connection ducts inside the shaft

For example, AFR 80 flexible aluminium duct between the main duct in the shaft and unit, max. 2 m long (→ approval).

Connection ducts outside the shaft

For example, AFR 80 flexible aluminium duct between the main duct in the shaft and unit, max. 6 m long (→ approval).

Duct elbows in the unit connection duct

max. 90° bend, ascending

Number of duct elbows permitted for wall installation

Max. 2 x 90°

Number of duct elbows permitted for ceiling installation

Max. 2 x 90°

Regulating equipment in the exhaust air duct

Not permitted

Wall/ceiling opening for DN 80 unit connection duct

Brickwork or concrete: 130 mm