Installation information
(Also Requirements in line with approval)
Housing without fire protection equipment.
Installation is permissible in the following installation positions:
- Wall installation With air outlet direction (exhaust socket) upwards, to the right, to the left or to the rear. Installation with UPM 60/100 mounting support or directly with the wall with ER-MS installation kit (hammer head screws and brackets) in the side mounting grooves.
- Ceiling installation and suspended ceiling: Installation with UPM 60/100 mounting support or directly with the ceiling with ER-MS installation kit (hammer head screws and brackets) in the side mounting grooves.
- Ceiling installation and non-suspended ceiling: Mounting directly on the ceiling.
Suitable mounting material is to be provided by the customer.
The plastic shutter should be prepared according to these instructions so that it closes fully sealed in the installation position.
The housing must be inserted without any distortion. Failure to do so will mean that the fan insert cannot engage correctly in the housing and the degree of protection stated on the rating plate is no longer ensured.
Break open the housing segment [S] below to use the ER-ZR second room connection set or the ER-AS extraction socket.
A toilet seat air extraction unit is connected to the housing using the ER-AS extraction socket (DN 75/80).
Use ER-MO expanded rubber for acoustic insulation of thin ceilings capable of resonance (System and accessory components).