Electrically connecting the unit
- Prior to accessing the connection terminals, switch off all supply circuits. Switch off mains fuse, secure against being accidentally switched back on and position a visible warning sign.
- Remove plaster protective cover.
- Cut off and insulate PE conductor and individual cable cores that are not required!
- Remove power cable’s sheathing and cut to length: Electrical connection.
- Wire power cable to the terminal box according to the wiring diagram: Wiring diagrams.
- Terminal 1 marked with triangle (▲) see wiring diagrams.
- Mark the fan type and connection type on the wiring diagram in the housing.
- This prevents mistakes during final installation, for example, if different fan inserts are fitted in the system.
- If desired, first fit a spacing or wall frame.
- Insert plaster protective cover.
Recommendation: Keep these installation instructions until the final assembly in the flush-mounted housing.