Fault rectification

Fault finding and repairs only permissible when carried out by qualified electricians.

Malfunction

Cause, measures

Fan does not switch on.

No mains voltage. Check whether the mains fuse has failed. Switch on if necessary.

ERR 10/1 … ERR 31/1, ERR 10/1 S and ERR 16/1 S: Thermal overload protection of the motor has triggered.

Motor too hot. Wait until motor and temperature limiter have cooled. Cool-down time can be up to 10 minutes. Only then switch the fan on again.

Fan does not switch on.

Impeller blocked. Check the impeller and clean the fan if necessary. Check the fan for unusual noises during operation.

Deposits on the impeller and in the housing caused by dust in the air.

Operation without air filter. Install air filter in duct system. Never clean the interior of the fan with water or a high-pressure cleaner.

Impeller does not rotate.

Switch off the fan. Make sure that the impeller is not blocked by foreign bodies.