Fault rectification

Fault finding and repairs only permissible when carried out by qualified electricians.

Unit may be energized even when at a standstill and may switch on automatically due to sensors (time delay, humidity etc.).

Risk of burning in the area of the motor

  1. Before working on the fan, switch off the mains fuse and secure with a padlock.
  2. Attach a warning sign in a clearly visible place.
  3. Let the fan cool down sufficiently before working in the area of the motor.

Malfunction

Cause, measures

Fan does not switch on/does not run.

No mains voltage, earth fault. Check whether the power supply is guaranteed (mains fuse, switch, motor connection).

Wiring not carried out correctly. Check wiring circuit diagram.

Thermal overload protection of the motor has triggered.

Motor too hot.

EZQ../EZS..: No measure. After it has cooled off, the motor automatically switches on.

DZQ../DZS..: Leave fan off until the motor and temperature limiter have cooled down (up to 30 minutes). Only then switch it back on.

The impeller is blocked or dirty.

Remove foreign objects or dirt.

Winding short

Replace fan.

Air flows in wrong direction (motor turns wrong direction).

Check wiring circuit diagram. Reverse polarity if necessary.

EZQ.. B/EZS.. B units: Fan doesn’t start up or motor too hot.

Capacitor not installed/incorrectly installed Connect the capacitor correctly.

EZQ.. B/EZS.. B units: Slight contact with the stationary impeller may cause the fan to start.

Capacitor not installed/incorrectly installed Connect the capacitor correctly.

EZQ.. B/EZS.. B units: Motor with wrong direction of rotation/air flow direction

Capacitor not installed/incorrectly installed Connect the capacitor correctly.