CO2-/VOC-/Rel. Humidity limit value min./max.
Parameters: CO2 limit value min
Set value: 500 ... 800 ... 900 ppm.
Parameters: CO2 limit value max
Set value: 1000...1230...2000 ppm.
Parameters: VOC limit value min.
Set value: 500...800...900 ppm.
Parameters: VOC limit value max.
Set value: 1000...1230...2000 ppm
Parameters: Humidity limit value min
Set value: 30 ... 35 ... 45 % r. h.
Parameters: Humidity limit value max
Set value: 50 ... 70 ... 90 % r. h.
With linear sensor control for ventilation (Auto Sensor operating mode), the volumetric flow varies in a continuously variable manner depending on the current CO2/VOC/rel. humidity concentration. Minimum limit values apply to reduced ventilation (RV) and maximum limit values for intensive ventilation (IV). Linear control is used between the two.
Example
For information on set value stepped or linear → Combi sensor operation.