Technical data
Nominal voltage | 230 V AC |
Power frequency | 50 Hz/60 Hz |
Power consumption, max. | 4 VA |
Contact (relay R1) | Changeover contact, potential-free |
Contact material | AgNi, cadmium-free |
Switching current, max: | |
with cos φ = 1 | 10 A |
with cos φ = 0.4 | 3 A |
Maximum load: | |
inductive load | 2 A |
ohm resistive load | 5 A |
Maximum switching capacity: | |
with cos φ = 1 | 2500 VA |
at DC | 240 W |
Setting range switching point (setpoint) | min. 1 m/s, max. 20 m/s |
Hysteresis fixed | approx. 3.5% of setpoint, min. 0.05 m/s |
Degree of protection: | |
Control unit | IP 30 |
Measuring probe | IP 20 |
Overvoltage category | II |
Degree of contamination | 2 |
Installation height | up to 2000 m above sea level (NN) |
Weight: | |
Control unit | 0.20 kg |
Measuring probe | 0.12 kg |
For more technical data → rating plate.