PP 45 RHK (540 mm) or PP 45 RHL (800 mm) shell sleeves are suitable for the MS 160 masonry block.
Shorten and deburr the shell sleeve according to the wall thickness. Observe the required projections for plaster, masonry, inner cover and external cover. For external covers → PP shell installation instructions, prescribed wall sleeve projection.
Fix the shell sleeve inside the masonry block with non-pressing or expansion-free construction foam. Centre the shell sleeve symmetrically in the core drill hole using the EPS shims. Cut off protruding construction foam and shims flush with the masonry block. ATTENTION: Note the gradient. Building damage due to condensation if installed incorrectly.
Information on PP 45 and PPB 30 units
PP 45: Use the recess shown in the figure to feed the connection cable. This is positioned in the PP 45 unit to match the line feedthrough.