Technical data
Rated voltage, 3 phases | 400 V |
Power frequency | 50 Hz / 60 Hz |
Maximum loading | 0.4 A |
Maximum loading | MV 16-1: 10 … 16 A |
Max. backup fuse | 80 A (Ue 415 V + 5 %) |
Max. power loss | approx. 8 W |
Radio interference suppression (EN 55011) | VDE 0875, interference level N |
Max. cable cross-section for | 6mm² |
Max. cable cross-section for TB/auxiliary switch | 2.5 mm² |
Motor switching capacity: IEC 60947-4-1, EN60947-4-1, VDE 0660-102 | AC, 3 max. 500 V |
Short-circuit breaking capacity: | 6 kA (400 V + 5 %), |
Emitted interference according to | EN 61000-6-3 |
Resistance to interference according to | EN 61000-6-2 |
Degree of protection | IP 55 |
Protection class | II |
Type of installation | Surface-mounted |
Weight | 0.6 kg |
Dimensions (WxHxD) | 80 x 135 x 96.5 mm |
Ambient temperature | -25 ... 40 °C |
For more technical data → rating plate.