RLS 45 O service menu
Bold | Factory settings |
LED flashes quickly | |
LED flashes slowly |
LEDs | Parameters | Set value / Binary display* | Setting / description |
Device type on RLS (Fan1/Fan2) | 1 | PP 45 The type family, which is connected to the Fan1/Fan2 fan interface, is selected here. Notice: Only single-type PP 45 or PPB 30 unit combinations are permitted at the fan interface! | |
Number of device pairs / devices on RLS (Fan1/Fan2) | 1 | 1 unit pair PP 45 or 1 PPB 30 2 unit pairs PP 45 or 2 PPB 30 3 unit pairs PP 45 or 3 PPB 30 Odd number 3 PP 45 units Odd number 5 PP 45 units The number of units connected to the fan interface (Fan1/Fan2) is selected here. | |
Ventilation levels | 1 | Ventilation level “0” possible | |
* The service menu items are set according to the 3-digit binary code 111, e.g. the adjuster "5" is displayed as 101 → Upper and lower LEDs light up. |
Bold | Factory settings |
LED flashes quickly | |
LED flashes slowly |
LEDs | Parameters | Set value / Binary display* | Setting / description |
Power units (LTs) or room air controls (RLS) | 0 | Operation without further LTs/RLS Adjuster for adding further room air controls (RLS) or power units (LTs) to this room air control. Example: Two further RLS (RLS #2 and #3) are connected to RLS #1. Set value = 2. Set set value 4 on RLS #2 and set value 5 on RLS #3. Notice: Only single-type RLS combinations are permitted! | |
Sensors | 0 | No sensor Select how many internal and external sensors are connected/combined. The PP 45 HYI internal sensor and the PP 45 HY, PP 45 CO2 and PP 45 VOC external sensors are available. | |
* The service menu items are set according to the 3-digit binary code 111, e.g. the adjuster "5" is displayed as 101 → Upper and lower LEDs light up. |
Bold | Factory settings |
LED flashes quickly | |
LED flashes slowly |
LEDs | Parameters | Set value / Binary display* | Setting / description |
ModBus settings | 1 | RS 485 inactive ModBus active 9600 Baud | |
ModBus address | 1 | Address 10 | |
* The service menu items are set according to the 3-digit binary code 111, e.g. the adjuster "5" is displayed as 101 → Upper and lower LEDs light up. |