PP 45 RC / PPB 30 RC fault messages
Red LED (*) | Fault |
Internal error in control Fault LED in alternation: lights up for extended period and then flashes briefly 1x. Fault rectification: Ensure that no voltage is present, restart the unit. To reset the unit, press: for 2 seconds. | |
Master-slave communication Fault LED in alternation: lit up for extended period and then flashes briefly 2x. Fault rectification: Check communication paths for radio signals and select a different positioning if necessary. If the fault still occurs, set the unit to “single-room ventilation unit” in the service menu. | |
Internal sensor defective (I2C) Fault LED in alternation: lit up for extended period and then flashes briefly 3x. Fault rectification: Check that the sensor is positioned correctly or replace the sensor. | |
External sensor not reporting Fault LED in alternation: lit up for extended period and then flashes briefly 4x. Fault rectification: Check sensor. | |
No communication with the EnOcean module PP 45 EO Fault LED in alternation: lit up for extended period and then flashes briefly 5x. Fault rectification: Check PP 45 EO module for functionality. |
The faults are not acknowledged. Acknowledgement takes place automatically when the fault is remedied.