Kombinationen K1–K18 (RLS 45 K)
Lüftungsgerät, Sensor | PP 45 O / PP 45 K | PPB 30 O | PPB 30 K | Abluftgeräte z. B. ER/ECA | Sensoren extern (PP 45 HY, CO2, VOC) und LT | Sensor intern PP 45 HYI | EnOcean Erweiterungsmodul PP 45 EO |
Kombination Nr. | Schnittstelle Fan1/Fan2 | Schnittstelle Fan1/Fan2 | RS 485 Bus | 230 V Eingang an RLS 45 K | RS 485 Bus | I2C Bus | RS 485 Bus |
K1 | 2 |
|
| 1 | 0-3 | 0-1 | 0-1 |
K2 | 3 |
|
| 1 | 0-3 | 0-1 | 0-1 |
K3 | 4 |
|
| 1 | 0-3 | 0-1 | 0-1 |
K4 | 5 |
|
| 1 | 0-3 | 0-1 | 0-1 |
K5 | 6 |
|
| 1 | 0-3 | 0-1 | 0-1 |
K6 |
| 1 |
| 1 | 0-3 | 0-1 | 0-1 |
K7 |
| 2 |
| 1 | 0-3 | 0-1 | 0-1 |
K8 |
| 3 |
| 1 | 0-3 | 0-1 | 0-1 |
K9 |
|
| 1 |
| 0-3 | 0-1 | 0-1 |
K10 |
|
| 2 |
| 0-3 | 0-1 | 0-1 |
K11 |
|
| 3 |
| 0-3 | 0-1 | 0-1 |
K12 | 2 |
| 1 |
| 0-3 | 0-1 | 0-1 |
K13 | 3 |
| 1 |
| 0-3 | 0-1 | 0-1 |
K14 | 4 |
| 1 |
| 0-3 | 0-1 | 0-1 |
K15 | 2 |
| 2 |
| 0-3 | 0-1 | 0-1 |
K16 |
| 1 | 1 |
| 0-3 | 0-1 | 0-1 |
K17 |
| 2 | 1 |
| 0-3 | 0-1 | 0-1 |
K18 |
| 1 | 2 |
| 0-3 | 0-1 | 0-1 |
Zusatzfunktionen
K1-K8: Zuluftfunktion für ER-Abluftbetrieb
K9-K11: Volumenstromausgleich ABL-Betrieb über Außenluftdurchlass ALD
K12-K18: Zuluftfunktion für PPB 30 K Abluftbetrieb.
Hinweis: Volumenstromausgleich nur für 1 PPB 30 K Gerät möglich.
* Bei der Verwendung von PP 45 EO können max. 8 Funksensoren und max. 4x PP 45 RC (Master) eingelernt werden.