External sensors

The connection of a wired external sensor, takes place on the RS 485 interface of the RLS 45 O / RLS 45 K control (max. 3 sensors per control).

Demand-driven operation (sensor-controlled automatic operation) only applies to ventilation units, which are connected to the same room air control as the sensors.

External sensors which can be connected

Connecting sensors

  1. Install and wire external sensor → Installation instructions for final installation kit.
  2. With external sensors, addressing is undertaken using the rotary switch on the sensor housing:

Position 0 = sensor 1, position 1 = sensor 2, position 2 = sensor 3

The sensors (external and internal) are only taught-in on the master.

  1. Take room air control out of flush-mounted box and wire sensor connection cable to plug-in connection terminal of RS 485 interface → Wiring diagrams in installation instructions for final installation kit.
  2. Insert room air control in the flush-mounted box and screw down to flush-mounted box with 2 screws.
  3. Fit front panel. Make sure it locks into position. With front covers, ensure that sensor opening (hole in front panel) is above the sensor.
  4. Commissioning ventilation system→ Commissioning.
  5. Activating sensor: In service mode → Installation instructions for final installation kit or with the (Commissioning software.