Technical data for PPB 30
External diameter | DN 160 |
Length of | PP 45 RHK: 500 mm |
Wall thickness | 320 – 790 mm |
Air filter | Filter class ISO 16890 |
Air volume/unit | 26 m³/h |
Degree of protection | IP X4 |
Sound pressure level: at distance of 1 m, free-field conditions (ventilation levels 1 - 5) | 18 / 32 / 41 / 45 / 49 dB(A) |
Rated voltage | PPB 30 O, PPB 30 K: 12 V |
Power frequency | 50/60 Hz |
Volumetric flow in heat recovery mode, ventilation levels 1 to 5 | 5 / 12 / 18 / 22 / 26 m³/h |
Volumetric flow in exhaust air mode (no heat recovery unit) | 45 m³/h |
Power consumption | 1.7 / 2.5 / 3.4 / 4.4 / 5.3 W |
Degree of heat provision | 73.3 % (level 3) |
SPI | 0.19 W / (m³/h) |
SEC value | A (-39,71 kWh / (m²*a)) |
Permissible ducting lengths with wired connection | From star point, max. 25 m per ventilation unit |
Weight of slide-in module, cpl. | 3.6 kg |
Radio components: Frequency range (in acc. with EN 300220-1) | 868.35 MHz |
Radio receiver with internal antenna | Do not mount on the wall side of the transmitter |
“Wireless” operating distances in the building are dependent on the building materials used: |
up to: |
DS 45 RC → PP 45 RC | 30 m |
PP 45 EO → PP 45 RC | 30 m |
PP 45 RC → PP 45 RC | 30 m |
With PP 45 RC as amplifier | 40 m |
For more technical data → rating plate.