Menu settings — operator

Factory settings in bold

Basic settings

Ventilation

Sensors

EnOcean wireless

Installer

 

Basic settings

Parameters

Set value

Luminosity of LED indicator

2, 3, 4, 5

Luminosity of LED standby

0, 1, 2

Time LED auto. Standby

0 ... 3 ... 6 minutes

Ventilation

Parameters

Set value

Filter service life, unit filter

1 ... 6 ... 8 months

Filter change, unit filter: Acknowledgement

changed, not changed

Duration of ventilation level 5 (intermittent ventilation)

5 ... 30 ... 90 minutes

Duration of night time level 0 (sleep mode)

15 ... 60 ... 120 minutes

Sensors

Parameters

Set value

Relative humidity limit value min. (HPV)

35 ... 35 ... 50 % r. h.

Relative humidity limit value max. (IV)

55 ... 60 ... 70 % r. h.

CO2 limit value min.

500 ... 800 ... 900 ppm

CO2 limit value max.

1000 ... 1200 ... 1500 ppm

VOC limit value min.

500 ... 800 ... 900 ppm

VOC limit value max.

1000 ... 1200 ... 1500 ppm

PPB 30 K relative humidity limit value min. (HPV)

35 ... 40 ... 45 % r. h.

PPB 30 K relative humidity limit value max. (IV)

50 ... 70 ... 85 % r. h.

 

EnOcean wireless

Parameters

Set value

Teaching mode

off, on

EnOcean unit list

EEP list

Teach-out units

 

The PP 45 EO EnOcean module can only be used in combination with the RLS 45 K control. The activation of the PP 45 EO and the teaching-in and teaching-out of radio components and devices is only possible with the commissioning software.