Technical data for PPB 30
External diameter |
DN 160 |
Length of |
PP 45 RHK: 500 mm |
Wall thickness |
320 – 790 mm |
Air filter |
Filter class ISO 16890 |
Air volume/unit |
26 m³/h |
Degree of protection |
IP X4 |
Sound pressure level: at distance of 1 m, free-field conditions (ventilation levels 1 - 5) |
18 / 32 / 41 / 45 / 49 dB(A) |
Rated voltage |
PPB 30 O, PPB 30 K: 12 V |
Power frequency |
50/60 Hz |
Volumetric flow in heat recovery mode, ventilation levels 1 to 5 |
5 / 12 / 18 / 22 / 26 m³/h |
Volumetric flow in exhaust air mode (no heat recovery unit) |
45 m³/h |
Power consumption |
1.7 / 2.5 / 3.4 / 4.4 / 5.3 W |
Degree of heat provision |
73.3 % (level 3) |
SPI |
0.19 W / (m³/h) |
SEC value |
A (-39,71 kWh / (m²*a)) |
Permissible ducting lengths with wired connection |
From star point, max. 25 m per ventilation unit |
Weight of slide-in module, cpl. |
3.6 kg |
Radio components: Frequency range (in acc. with EN 300220-1) |
868.35 MHz |
Radio receiver with internal antenna |
Do not mount on the wall side of the transmitter |
“Wireless” operating distances in the building are dependent on the building materials used: |
up to: |
DS 45 RC → PP 45 RC |
30 m |
PP 45 EO → PP 45 RC |
30 m |
PP 45 RC → PP 45 RC |
30 m |
With signal amplification on EnOcean radio sensors and radio switches with EEP protocol |
40 m |
For more technical data → rating plate.