PPB 30 RC service menu

Bold

Factory settings

LED flashes quickly

LED flashes slowly

 

PPB 30 RC LEDs

Parameters

Set value

Setting / description

The orange operating mode LED flashes 1x per cycle

Operating modes

1
2

Automatic operation (red LED 1x)
system operation (red LED 2x)

Two operating modes can be selected here.
Automatic operation: Unit usually works autonomously according to internal sensor.
System operation: The unit usually works according to the controller specifications. For more detailed description → Operating instructions.

The orange operating mode LED flashes 2x per cycle

Sensor

0
1
2

inactive (red LED OFF)
active 40 % - 70 % r. h. (red LED 1x)
active 45 % - 80 % r. h. (red LED 2x)

The limit values of the integrated humidity sensor can be set or deactivated here.

The orange operating mode LED flashes 3x per cycle

Ventilation levels

0
1

Ventilation levels Off possible (red LED OFF)
Ventilation level Off blocked (red LED 1x)

With the ventilation level “0” blocked setting, the ventilation units cannot be switched off on this control. The units then run with at least ventilation level 1.

The orange operating mode LED flashes 4x per cycle

Selection of auto/manual dehumidification function

1

2

3

4

Exhaust air mode Automatic / Manual exhaust air mode (red LED 1x)
Automatic exhaust air mode / Manual intensive ventilation (red LED 2x)
Automatic intensive ventilation / Manual exhaust mode (red LED 3x)
Automatic intensive ventilation / Manual intensive ventilation (red LED 4x)
The dehumidification function for the sensor (Auto) and for the button (Manual) can be set here.

Bold

Factory settings

LED flashes quickly

LED flashes slowly

 

PPB 30 RC LEDs

Parameters

Set value

Setting / description

The blue operating mode LED flashes 1x per cycle

Duration of
intermittent ventilation/
ventilation level

1
2
3

5 minutes (red LED 1x)
10 minutes (red LED 2x)
30 minutes (red LED 3x)

Parameters for the duration of the manual dehumidification function (level 5) and the duration of the ventilation level when overriding demand-driven operation are set here (factory setting 10 minutes).

The blue operating mode LED flashes 2x per cycle

Sleep function

1
2
3

30 minutes (red LED 1x)
60 minutes (red LED 2x)
90 minutes (red LED 3x)
The duration of the sleep function (level 0) is parameterised here
(factory setting 60 minutes).

The blue operating mode LED flashes 3x per cycle

Filter runtime

1
2
3
4

2 months (red LED 1x)
3 months (red LED 2x)
6 months (red LED 3x)
Reset filter runtime (red LED 4x)
.The filter runtime is parameterised here (factory setting 6 months).

The blue operating mode LED flashes 4x per cycle

Single-room ventilation unit

1
2

Operation in pairs (red LED 1x)
single-room ventilation unit (red LED 2x)

If there are reception problems with the slave or master device, the PPB 30 RC unit can be enabled as a single-room ventilation unit.