Volumetric flow of ventilation level

Reduced ventilation RV (in m³/h)

Type

Min.

Factory set

Max.

WS 310 / WS 320 ..

80

120

320

WS 410 / WS 470 ..

80

160

490

WS 170

40

60

160

WS 160 Flat

40

60

160

WS 300 Flat

80

100

300

Trio

40

60

120

Nominal ventilation NV (in m³/h)

Type

Min.

Factory set

Max.

WS 310 / WS 320 ..

80

180

320

WS 410 / WS 470 ..

80

240

490

WS 170

40

90

160

WS 160 Flat

40

90

160

WS 300 Flat

80

150

300

Trio

40

90

120

Intensive ventilation IV (in m³/h)

Type

Min.

Factory set

Max.

WS 310 / WS 320 ..

80

240

320

WS 410 / WS 470 ..

80

320

490

WS 170

40

120

160

WS 160 Flat

40

120

160

WS 300 Flat

80

200

300

Trio

40

120

120

The volumetric flow setting applies to both fans. With humidity protection ventilation, the fans run in intermittent operation. We recommend setting the volumetric flow for NV first.

The RV and IV volumetric flows are set automatically by the control on the basis of the NV reference value 1/3 less than (RV) and 1/3 greater than (IV).

Example WS 310/410, WS 320/470, WS 300 Flat:
NV 150 → RV 100 → IV 200

Example WS 170, WS 160 Flat, Trio:
NV 90 → RV 60 → IV 120

The IV and RV control values can then be set manually.

Condition: Volumetric flow Intensive ventilation
> Nominal ventilation > Reduced ventilation.