Maximum room temperature
Parameters: Maximum room temperature
Set value: 18 ... 24 ... 30°C
The control releases cooling via the bypass when the set maximum room temperature is reached (measurement on temperature sensor).
Conditions for cooling via the bypass
● T outside air > 5° C with single control unit in solo mode
and
●T outside air < T room reference and T room reference > maximum room temperature