Replacing the air filter

Change the air filters when the filter change indicator lights up, but after 1 year at the latest!

Only use original replacement filters.

EPM 1 50% filters (F7) are used for the outside air and ePM 10 50% filters (M5) for the exhaust air. The filters serve as protection for the heat exchanger and ensure good air quality. The condition of the filters should be checked regularly (2-4 times a year). The filters must be replaced if necessary, at the latest after 1 year. Heavily soiled filters can cause the following faults:

Change the filter:

  1. Note the safety instructions Safety instructions!
  2. Release the quick-release clips and open the front inspection door.
  3. Remove the air filters from the ventilation unit.
  4. Dispose of the air filters in accordance with local regulations.
  5. Clean the filter guides with a damp cloth and allow them to dry.
  6. Insert new air filters in such a way that the filters can be pushed in as far as they will go without tension. Pay attention to the direction of the air.
  7. Close the inspection doors. Fasten them with the quick-release clips.

Replacement filter

Unit type

Filter exhaust air ePM 10 50% (M5), item no.:

Filter outside air, ePM 1 50% (F7), item no.:

RLT 1200 MV4512

0043.2800

0043.2801

RLT 1600 MV4516

0043.2804

0043.2805

RLT 2300 MV4523

0043.2808

0043.2809

RLT 4000 MV4540

0043.2812

0043.2813

RLT 5500 MV4555

0043.2816

0043.2817