Electrical specifications of the RLT units
Model | Performance details | RCD details | |||
---|---|---|---|---|---|
Standard unit | PH | EH | Recom. type | Currently recorded RC | |
[kW] | [kW] | [kW] | [mA] | ||
M4512 H/V | 1.1 | 3.75 | 3.75 | B or B+ | 30 |
M4516 H/V | 1.6 | 5.25 | 5.25 | B or B+ | 30 |
M4523 H/V | 2.2 | 6.75 | 6.75 | B or B+ | 30 |
M4540 H/V | 3.7 | 13.5 | 13.5 | B or B+ | 300 |
M4555 H/V | 5.46 | 18 | 18 | B or B+ | 300 |
Model | Cable cross-sections | ||||||||
---|---|---|---|---|---|---|---|---|---|
Standard unit | Unit+PH & Unit+EH | Unit+PH+EH | |||||||
Maximum current | Rec. cable | Rec. fuse | Maximum current | Rec. cable | Rec. fuse | Maximum current | Rec. cable | Rec. fuse | |
[A] | [mm2] | [A] | [A] | [mm2] | [A] | [A] | [mm2] | [A] | |
M4512 H/V | 5.1 | 5x2.5 | 16 | 9.9 | 5x2.5 | 16 | 17.1 | 5x2.5 | 20 |
M4516 H/V | 7.1 | 5x2.5 | 16 | 13.8 | 5x2.5 | 16 | 23.8 | 5x2.5 | 25 |
M4523 H/V | 3.7 | 5x2.5 | 16 | 16.5 | 5x2.5 | 16 | 29.3 | 5x2.5 | 32 |
M4540 H/V | 6.1 | 5x2.5 | 16 | 31.7 | 5x4 | 16 | 57.4 | 5x2.5 | 63 |
M4555 H/V | 8.7 | 5x2.5 | 16 | 42.9 | 5x6 | 16 | 77.1 | 5x2.5 | 80 |
The cable cross-section calculations are based on a maximum cable length of 50 m and a voltage drop of 10 % of the supply voltage. For other installations, please contact Maico! |
Earthing of the RLT unit is absolutely essential!
The motor is "intrinsically safe" against overload. It is therefore not necessary to install electrical overload protection.
Single-phase – three-phase changeover (only for RLT 1200 and RLT 1600 WITHOUT electric heating register)
All units are manufactured at the factory with three-phase connections. If single-phase operation is required, please proceed according to the specified instructions.
Single-phase operation only applies to RLT 1200 and 1600 WITHOUT electric heating register!
All changes for the three-phase/single-phase conversion must be made on the power supply side of the circuit-breaker.