Alarm list

No

Alarm text

Delay

Description

Measures

1

Fault Supply air fan 1

200 s

Fault Supply air fan 1

The fan blower must be checked

6

Fault Exhaust air fan 1

200 s

Fault Exhaust air fan 1

The range hood must be checked

11

Alarm Supply air fan 1

0 s

Alarm from SAF frequency converter via Modbus communication

The fan blower must be checked

16

Alarm Exhaust air fan 1

0 s

Alarm from frequency converter EAF 1 via Modbus communication

The range hood must be checked

21

Warning Supply air fan 1

0 s

Alarm from frequency converter SAF 1 via Modbus communication

The fan blower must be checked

26

Warning Exhaust air fan 1

0 s

Warning from frequency converter EAF 1 via Modbus communication

The range hood must be checked

56

Anti-freeze grid

0 s

External frost protection thermostatically activated

The value of the freezing temperature sensor is below the specified limit value

57

Defrost monitor exchanger

0 s

Exchanger de-icing pressure switch activated

The value of the defrost temperature sensor is below the specified limit value

58

Fire alarm

0 s

Fire alarm activated

Check the connections of the fire status information of the corresponding terminal

59

Smoke detector

0 s

Smoke detector activated

Check the connections of the smoke status information of the corresponding terminal

63

Electric heater is overheated

0 s

Heating high temperature limit switch activated

Failure of the electrical heating at high temperature. Check whether there is an air flow. Check the cable connections of the heater. Disconnect the power supply and check the heater.

68

Filter-1 is dirty

0 s

Filter-1 Contamination at the digital input

Check whether the filter on the fresh air side is dirty

69

Filter-2 is dirty

0 s

Filter-2 Contamination at the digital input

Check whether the filter on the return air side is dirty

71

SAF motor protection switch

0 s

SAF motor protection switch at the digital input

Check SAF motor protection switch

72

EAF motor protection switch

0 s

EAF motor protection switch at the digital input

Check EAF motor protection switch

73

DX interference

0 s

DX interference at the digital input

Check the connection of the DX error information on the corresponding terminal

78

Internal battery fault

0 s

Internal battery must be replaced

Internal battery must be replaced

81

Deviation alarm supply air temp.

30 min

Supply air temperature deviates too much from the setpoint value

Check the supply air temperature sensor and the coils

86

High supply air temperature

5 s

Supply air temperature too high

The supply air is above the specified limit value. Check the heating drive or the electric heating.

87

Low supply air temperature

5 s

Supply air temperature too low

The supply air is below the specified limit value. Check cooling valve or DX unit.

90

High room temperature

30 min

Room temperature too high with room temperature control

The room temperature is above the specified limit value. Check the temperature control equipment, heating valve, DX unit, etc.

91

Low room temperature

30 min

Room temperature too low with room temperature control

The room temperature is below the specified limit value. Check the refrigerant control system, refrigerant valve, DX unit, etc.

113

Manual operation of the ventilation unit

0 s

The unit is in manual mode

The unit must be in OFF mode. If not, check the manual mode parameters.

114

Manual operation Supply air

0 s

Supply air temperature controller with manual control

Check manual mode parameters

115

Manual operation Supply air fan

0 s

Supply air fan with manual control

Check manual mode parameters

116

Manual operation Exhaust air fan

0 s

Exhaust air fan with manual control

Check manual mode parameters

117

Manual mode Heating

0 s

The heater is in manual mode

Check manual mode parameters

118

Manual operation Heat exchanger

0 s

Heat exchanger output with manual control

Check manual mode parameters

119

Manual operation Cooler

0 s

Cooling capacity with manual control

Check manual mode parameters

120

Manually operated shutter

0 s

Shutter performance with manual control

Check manual mode parameters

128

Manual control sequence A

0 s

Manual control of sequence A

Check manual mode parameters

129

Manual control sequence B

0 s

Manual control of sequence B

Check manual mode parameters

130

Manual control sequence C

0 s

Manual control of sequence C

Check manual mode parameters

131

Manual control sequence D

0 s

Manual control of sequence D

Check manual mode parameters

132

Manual control sequence E

0 s

Manual control of sequence E

Check manual mode parameters

138

Output in manual mode

0 s

Analogue or digital output in manual mode

Check manual mode parameters

139

Input in manual mode

0 s

Analogue or digital input in manual mode

Check manual mode parameters

143

Pre-treatment in manual mode

0 s

Pre-treatment in manual mode

Check manual mode parameters

144

Sensor error Outside air temperature

5 s

Fault in the connected sensor

Check the corresponding sensor connections

145

Sensor error Intake air temperature

5 s

Fault in the connected sensor

Check the corresponding sensor connections

146

Sensor error Supply air temperature

5 s

Fault in the connected sensor

Check the corresponding sensor connections

147

Sensor error Exhaust air temperature

5 s

Fault in the connected sensor

Check the corresponding sensor connections

148

Sensor error Exhaust air temperature

5 s

Fault in the connected sensor

Check the corresponding sensor connections

149

Sensor error Room temperature

5 s

Fault in the connected sensor

Check the corresponding sensor connections

165

Sensor error Supply air pressure

5 s

Fault in the connected sensor

Check the corresponding sensor connections

166

Sensor error Exhaust air pressure

5 s

Fault in the connected sensor

Check the corresponding sensor connections

167

Sensor error Supply air flow rate

5 s

Fault in the connected sensor

Check the corresponding sensor connections

168

Sensor error Exhaust air flow

5 s

Fault in the connected sensor

Check the corresponding sensor connections

171

Sensor error Defrost temperature

5 s

Fault in the connected sensor

Check the corresponding sensor connections

175

Sensor error CO2 room/exhaust air

5 s

Fault in the connected sensor

Check the corresponding sensor connections

176

Sensor error Room/external air humidity

5 s

Fault in the connected sensor

Check the corresponding sensor connections

192

Device for communication disturbances

0 s

Communication error to the supply/exhaust air fan driver

Check the communication lines

194

Internal error

60 s

The configuration of a physical output to more than 1 function leads to undefined behaviour of the controller

Check the positions of all digital and analogue outputs