Configuring/activating sensor
- Connect the PC/notebook to the ventilation unit (USB) → Front side of ventilation unit.
- Call up commissioning software. Select USB connection. The start screen appears.
- Call up the Installer parameter and enter the service code. The programme changes to the Installer level.
- Select the Device settings/Sensors parameter.
- Activate the desired sensor (1, 2, 3 or 4), set to CO2 and name it. The name appears on the main control unit.
- Set the CO2 limit value min. and CO2 limit value max..
Setting value for CO2 limit value min.:
500 ... 800 ... 900 ppm (factory setting 800 ppm)
Setting value for CO2 limit max.:
1000...1230...2000 ppm (factory setting 1230 ppm)
- CO2 control voltage 0 V: Setting value 0 ppm
CO2 control voltage 10 V: Setting value 2000 ppm - Remove USB cable, test settings and functions.
For further information on parameterisation and setting values →Internet version of the installation, commissioning and maintenance instructions of the WS 120 Trio ventilation unit, Unit settings/Sensor settings menu.
Download the instructions at www.maico-ventilatoren.com.