Configuring/activating air quality controller

The sensor can be parameterised with the commissioning software or on the optional RLS T2 WS control unit.

  1. Connect the PC/notebook to the ventilation unit (USB) → Front side of ventilation unit.
  2. Call up commissioning software. Select USB connection. The start screen appears.
  3. Call up the Installer parameter and enter the service code. The programme changes to the Installer level.
  4. Select the Device settings/Sensors parameter.
  1. Activate the desired sensor (1, 2, 3 or 4), set to VOC and name it. The name appears on the main control unit.

Minimum limit values apply to reduced ventilation (RV) and maximum limit values for intensive ventilation (IV). Linear control is used between the two.

  1. Set the VOC limit value min. and VOC limit value max..
    Setting value for VOC limit value min.:
    500 ... 800 ... 900 ppm (factory setting 800 ppm)
    Setting value for VOC limit max.:
    1000...1230...2000 ppm (factory setting 1230 ppm)

Be sure to set the sensor’s VOC control voltage for 0 V and 10 V as follows.

  1. VOC control voltage 0 V: Setting value 0 ppm
    VOC control voltage
    10 V: Setting value 2000 ppm
  2. Remove USB cable, test settings and functions.

For further information on parameterisation and setting values →Internet version of the installation, commissioning and maintenance instructions of the WS 120 Trio ventilation unit, Unit settings/Sensor settings menu.