Changing unit filters
A pending filter change is displayed on a main control unit (if the status display is switched on under basic settings). On the RLS 1 WR control unit, the LED of ventilation level II flashes regularly at longer intervals.
- Switch off ventilation unit.
WS 160 Flat
1 | Filter cover |
G4 | Air filter |
F7 | Pollen filter, alternatively active carbon filter |
WS 300 Flat
- Take filter covers out of the ventilation unit. CAUTION: Risk of injury from falling filters. When working at height, observe applicable accident prevention requirements.
- Pull the air filter/pollen filter out of the ventilation unit.
- Carefully slide the new filters into the filter shaft. NOTICE: Do not press the filters in (cellulose). Only press in at reinforced corners. Make sure that the air direction arrow is facing downwards.
- Close filter openings with the filter covers. Ensure correct installation.
- Reset filter change interval. To do this, click on the message on the RLS T2 WS screen and confirm the filter change with changed. Also confirm a premature filter change with "changed". For systems with a single RLS 1 WR, press the two arrow keys on the control unit together for 2 seconds. The 3 LEDs flash briefly. If resetting prematurely, press the keys at the same time for 10 seconds.
- Dispose of used filters in accordance with local regulations.