Brine EHE (ZP 1)

For additional board ZP 1 see accessories

Additional circuit board ZP 1 can be used to control a brine EHE with a regulated or unregulated pump.

Parameters: Brine earth heat exchanger

Set value: no / yes

Parameters: Brine circulation pump regulation

Set value: regulated / unregulated

Parameters: T air inlet offset heating

Set value: 0 ... 2 ... 5 K

Parameters: T air inlet, hysteresis heating

Set value: 1 ... 6 K

Parameters: T air inlet, hysteresis cooling

Set value: 2 ... 6 K

Requirements for the use of ZP 1

DIP switch of ZP 1 set to brine earth heat exchanger and activated with brine earth heat exchanger parameter.

Conditions for heating

Switch on brine CP when

Switch off brine CP with unregulated pump when

Switch off brine CP with regulated pump when

Conditions for cooling

Switching on brine CP

The air is cooled when all 3 conditions are met:

To prevent the circulation pump from synchronising, the temperature at the air inlet must be greater than the minimum air inlet temperature by the set amount of hysteresis.

Switching off brine CP

The air is no longer cooled if one of the following conditions is met:

● TR (room temperature) < set maximum room temperature → Room temperature adjustment

or

● T air inlet (air temperature in outside air connector) < T supply air min cooling → T supply air min. cooling

The circulation pump switches off if the temperature at the T air inlet sensor falls below the minimum T air inlet because the minimum supply air temperature T supply air min. cooling cannot be maintained.

With a regulated pump, when the switch-on temperature is reached, a defined voltage is set so that the T supply air min. cooling is reached. The temperature can then be maintained with the minimum use of energy. The pump is switched off as soon as the defined voltage falls to 0 V, as input on the control.