Manual operating mode
The ventilation unit runs at one ventilation level, until another level or operating mode is selected – with intermittent ventilation, time-limited increase to intensive ventilation.
When operating with an RLS 1 WR or EnOcean wireless components, the operating modes described apply.
Up to firmware version 1.2.7, the unit excess humidity protection is permanently activated in Manual mode; as of firmware version 1.3.0, there is no permanent activation.
All measurements from internal and external humidity sensors are used for analysis. If the maximum humidity value limit is exceeded, a switch is made to intensive ventilation until the humidity is 3 % below the value limit. The ventilation level is only increased to intensive ventilation if the outside air conditions are actually suited to dehumidification.