Switching contact function
With pre-heating/supplementary heating, incorrect installation will result in unit damage.
If external pre-heating or supplementary heating is selected, the power supply for the component should be switched via an external relay.
Parameters: Switching contact
Set value: Alarm, filter message, operating display, shutter, supplementary heating, pre-heating, brine EHE (unregulated pump), cooling. One of the aforementioned external components can be switched with the potential-free switching contact (max. 5 A) of the basic circuit board (main circuit board).
Additional settings for supplementary heating switching points
- Under `Switching contact´, select the `Supplementary heating´ parameter.
- Under `Supplementary heating´
• Set `Supplementary heating´ parameter to yes.
• Adjust switching point with `Hysteresis setpoint temperature´.
• Set `Supplementary heating´ parameter to no.
Additional settings for brine earth heat exchanger switching points
- Under `Switching contact´, select the `Brine earth heat exchanger´ parameter.
- Under `Brine earth heat exchanger´
,• set the `Brine earth heat exchanger´ parameter to yes.
• Adjust switching points using `T air inlet offset heating´, `T air inlet hysteresis heating´ and `Air inlet hysteresis cooling´ parameters.
• Set `Brine earth heat exchanger´ parameter to no.