Room temperature adjustment
Parameters: Room temperature adjustment
Set value: -3 ... 0 ... +3 K
Causes for deviation in actual room temperature:
● Unfavourable installation location for the touchscreen control unit, an external room sensor or bus room sensor.
● Exhaust air temperature sensor tolerance too high.
This parameter can be used to adjust the actual room temperature. The adjustment is based on the room sensor selected under room sensor configuration .
Example: Actual room temperature measured on touchscreen control unit = 20.3 °C. With Room temperature adjustment of -0.4 K, an actual room temperature of 19.9 °C is displayed.