Maximum room temperature

The minimum temperature difference between the Room Setpoint Temperature parameter and the maximum room temperature is 2 °C. If the temperature falls below the permissible temperature difference, an automatic correction is made.

Parameters: Maximum room temperature

Set value: 18 ... 24 ... 30 °C

The control releases cooling via the bypass when the set maximum room temperature is reached (measurement on temperature sensor).

Conditions for cooling via the bypass

● T outside air > 5° C with single control unit in solo mode

and

●T outside air < T room reference and T room reference > maximum room temperature