Filter monitoring (ZP 2)
For additional board ZP 2 see accessories
Parameters: Filter monitoring
Set value: No / Yes
Parameters: Permissible delta p
Set value: 30 - 100 %
Parameters: Start initialisation Filter characteristic curve
Alternative monitoring of filter usage times using pressure measuring sensor.
This involves determining a differential pressure and saving a pressure loss characteristics curve for every volumetric flow (HPV, RV, NV, IV) with clean filters.
The `Permissible delta p´ parameter specifies the maximum permissible increase in pressure in %.
This initialisation sequence takes place whenever a filter change is acknowledged.
For additional information about filter monitoring → accessories instructions.