WS 75 – Wiring diagram 3
A1 | Ventilation unit, Powerbox WS 75 |
W1 | 230 VAC connection cable |
W2 | 230 VAC connection cable for outside air fan (LIYY 4 x 0.5mm²) |
W2' | 230 VAC connection cable for outgoing air fan (LIYY 4 x 0.5mm²) |
DI1 | Digital input 1 / status input 1: Outside air/supply air fan Select contact type depending on function. Note configuration of digital inputs. |
DI2 | Digital input 2 / status input 2: Outside air/supply air fan Select contact type depending on function. Note configuration of digital inputs. |
DI3 | Digital input 3 / status input 1: Exhaust air/outgoing air fan Select contact type depending on function. Note configuration of digital inputs. |
DI4 | Digital input 4 / status input 2: Exhaust air/outgoing air fan Select contact type depending on function. Note configuration of digital inputs. |
W7 | Connection cable for multi-function contact MFC. Potential-free feedback and function relay contact max. 230 VAC/5 A // 30 VDC/5 A. Note configuration. |
W8 | Connection cable for external unit release (optional) or safety device. 12 VDC contact potential. External contact type to be used: NC |