CO2 limit value min / max, VOC limit value min / max

The sensor control of the ventilation (Auto Sensor operating mode) varies the volumetric flow continuously depending on the current CO2/VOC concentration. Minimum limit values apply to reduced ventilation (RV) and maximum limit values for intensive ventilation (IV). Linear control is used between the two.

Setting values
● CO2 limit value min: 500 ... 800 ... 900 ppm
● CO2 limit value max: 1000 ... 1230 ... 2000 ppm
● VOC limit value min: 500 ... 800 ... 900 ppm
● VOC limit value max: 1000 ... 1230 ... 2000 ppm