Product description
- Decentralised heat recovery unit with air@home control.
- Integrated Ethernet interface for linking to networks and for operational monitoring and control via the free air@home app (Android / iOS) or www.air-home.de web tool.
- Integrated USB-B socket for configuring the geniovent.x unit using free commissioning software on a laptop / PC.
- CO2 sensor for demand-driven ventilation integrated as standard.
- Low energy consumption thanks to 3-D impellers that are bent backwards. Degree of heat provision up to 95 %.
- Fans, with particularly energy-saving DC motors.
- Supply air and exhaust air volumes for ventilation levels 1, 2 and 3 can be set separately. Air volumes can be set in continuously variable manner.
- Volumetric flow ranges of 150...560 m³/h and 200...830 m³/h.
- The highest permitted resistance in the channel system at maximum ventilation power is 50 Pa. Increased resistance in the channel system reduces the ventilation power.
- The unit covers should be opened with a tool.
- Simple filter replacement, filter is freely accessible once the covers have been opened. Pollen filter of filter class ePM1 55% (F7) in the outside air and air filter of filter class ePM 10 60% (M5) in the exhaust air.
- Frost protection monitoring prevents the heat exchanger from freezing at low outdoor temperatures.
- Cross-counterflow heat exchanger (variant G): For transferring exhaust air heat to the supply air.
- Enthalpy heat exchanger (variant E): In addition to heat, the heat exchanger recovers some of the humidity from the room.
- Bypass: Used to bypass the heat exchanger. On summer nights, for example, slightly cooler air can be blown in.
- 2x DN 250 duct connections.
- All units with cross-counterflow heat exchanger (variant G) are equipped with a condensate lift pump. The connection diameter is 7 mm (inside), 10 mm (outside).
- RLS 1 WR control panel (item no. 0157.0809, included 1x in the scope of delivery) with the functions: On/off, 4 levels, filter replacement and fault display.