Installing the geniovent.x 600-900 S top box (optional)
- Top box for an installation setup where the ventilation unit can freely blow out and draw in air.
- With grille for supply air and exhaust air ducting.
- For geniovent.x 600 S/900 S units ‒ individual adaptation of connection sockets upon ordering.
- The top box is screwed to the housing cover of the ventilation unit at 6 positions, see through holes on the top of the ventilation unit.
- Scope of delivery: Top box and (6x M5x55 mm mounting material, 6 nuts with shims), these installation instructions.
- Remove mounting material bag from outgoing air socket.
- Lift up top box and thread condensate hose of ventilation unit through hole on underside of top box. Pull condensate hose out of outgoing air opening.
- Place top box on ventilation unit ‒ requires at least 2 people, note safety instructions. Do not pinch condensate hose.
- Open doors of ventilation unit. Reach through duct openings for exhaust and supply air.
- Push through insulation material at holes in housing cover of ventilation unit. Screw down top box to ventilation unit with the mounting material supplied (6 screws).
The cover flaps will be damaged if opened by hand.
Do not operate the cover flaps by hand.