Installation

Shutter does not close correctly if it is installed under tension.

  1. In order to guarantee the shutter function, only mount the shutter on a flat surface.

Minimum distance “X” to EZQ/DZQ and EZF/DZF fans

 

EZQ, DZQ

EZF, DZF

RS 20

185

160

RS 25

215

190

RS 30

245

210

RS 35

275

245

RS 40

305

265

RS 45

330

320

RS 50

370

320

RS 60

430

  1. Open the lamellae of the shutter, align the shutter.
  2. Mark the 4 drilling positions of the fixing holes, drill and insert the dowels.
  3. Place the protective grille on the back of the shutter.
  4. Screw the shutter including the protective grille to the wall with 4 screws.
  5. Fit the two deflection sleeves.
  6. Guide the pull cord through the wall/deflection sleeves.
  7. Attach the cord clamp at the installation site.
  8. Cut the pull cord to length and attach the pulling knob.
  9. Run function test. The shutters must open and close completely.