Connecting sensor
The Trio CO2 E sensor or Trio VOC E air quality controller is usually connected to the ventilation unit connection W8 or W9.
If the RLS 1 WR control unit is deactivated (Single control unit parameter inactive), connection W10 or W11 (sensor 3 or 4) can be used. The power supply to sensor 3 or 4 can be ensured via terminals LD1, LD2, LD3 (all 12 V DC) or with double assignment, via the 24 V DC supply of sensor connections.
With the ventilation unit prepared as before, proceed as follows:
- Connect the sensor on the main board according to the wiring diagram.
- Slide the electronics slide-in module into the two guide rails of the ventilation unit and screw it in place with the retaining bolt.
- Fit front cover and hand-tighten the 6 screws. Ensure that the front cover is positioned correctly and no infiltration air can be drawn in.