Intended use
This ventilation unit with heat recovery is used in centralised or decentralised ventilation systems. The unit provides controlled ventilation and air extraction in, for example, offices, school classrooms and other similar spaces. The units are intended for ceiling-mounted installation because they have outside air/outgoing air sockets on the sides and/or discharging upwards. Please note that the unit is very heavy, weighing approx. 210 kg. The unit may only be used if installed permanently, in dry indoor spaces and with connected ventilation ducts. DN 250 connection for geniovent.x 600 and DN 315 connection for geniovent.x 900. The units do not have a unit switch. Scope for completely disconnecting the unit from the power supply should be provided by the customer. The ventilation units are only intended for domestic use and similar purposes. Any other use or use that goes beyond this is considered improper use.
Regulations for operation with fireplaces:
The ventilation unit may only be installed in residential units with air-ventilated fireplaces if:
- The evaluation criteria drawn up by the responsible, regional master chimney sweep are met;
- Parallel operation of air-ventilated fireplaces for liquid or gaseous fuels and the air-extracting equipment can be prevented via safety devices, or the extraction of exhaust gas from the air-ventilated fireplaces is monitored by special safety devices. In the case of air-ventilated fireplaces for liquid or gaseous fuels, the fireplace or the ventilation system must be switched off if the safety device is triggered. In the case of air-ventilated fireplaces for solid fuels, the ventilation system must be switched off if the safety device is triggered.